6. Description of Parameters
- 157 -
6
Figure 6-51 Counting function
DIx
DIx
Allocate DIx with the
counter input function.
Any of F4-04
to F4-09 =26
Allocate DIx with the
counter reset function.
U0-12
Count value
Fb-08
Set count value
Clear to 0
Compare
DO
Any of F5-00
to F5-05 = 8
Reset
Allocate DO with the set
count value reached function.
DO outputs the set count
value reached signal.
Any of F4-04
to F4-09 = 25
Fb-09
Designated
count value
DO
DO outputs the
designated count
value reached signal.
Reset
Any of F5-00
to F5-05 = 8
Allocate DO with the
designated count value
reached function.
Count reset input
Output of set count
value reached
Count pulse input
U0-12 (Count value)
Fb-08 = 11
U0-12 = 11
1 2 3 10 11 12
U0-12 = 0
19 20 21
Fb-09 = 20
U0-12 = 20
1 2
Output of designated
count value reached
The settings of related function parameters in the preceding gure are as follows:
Function Code Parameter Name Setting Description
Any of F4-00 to F4-09 DIx function selection 25 Counter input
Any of F4-00 to F4-09 DIx function selection 26 Counting reset
Any of F5-00 to F5-05 DOx function selection 8 Set counting value reached
Any of F5-00 to F5-05 DOx function selection 9 Designated counting value reached
Note
For high pulse frequency, use terminal DI5.
You cannot allocate "Set counting value reached" function and "Designated
counting value reached" function to the same DO terminal.
The counter keeps counting in the drive running/stop status. It stops counting
until the set counting value is reached.
The counting value is retentive at power down.
An automatic stop system can be implementing by connecting the output
counting value reached signal of DO to the stop input terminal.