6. Description of Parameters
- 163 -
6
5. Set frequency reference
When frequency reference setting channel is communication and A7-00 = 1 (user
programmable card is enabled), frequency reference of the AC drive is determined by
setting of A7-06.
You can implement control of frequency reference of AC drive via PLC program by
operating corresponding D component.
Function Code Parameter Name Setting Range Default
A7-06
Setting frequency reference
via the user programmable
card
-100.00% to 100.00% 0.00%
The base value of this parameter is F0-10 (Max. frequency).
6. Set torque reference.
When torque reference setting channel is communication and A7-00 = 1 (user
programmable card is enabled), torque reference of the AC drive is determined by
setting of A7-07.
You can implement control of torque reference of AC drive via PLC program by
operating corresponding D component.
Function Code Parameter Name Setting Range Default
A7-07
Setting torque reference via
the user programmable card
-200.0% to 200.00% 0.0%
The base value of this parameter is rated motor torque.
7. Set user-dened faults.
When A7-00 = 1 (user programmable card is enabled), you can set user dened faults
Err80 to Err89 by operating corresponding D component to change setting of A7-09 in
the range of 80 to 89.
Function Code Parameter Name Setting Range Default
A7-09
Setting torque reference via
the user programmable card
0: No fault
80 to 89: User dened fault
code
0
If setting of A7-09 is out of 80 to 89, the setting will not take effect.