3. Electrical Installation
- 45 -
Type Terminal 
Name
Description
Digital 
outputs
DO1 CME Digital output 1 Optically-coupled isolation, dual-polarity 
open-collector output
Output voltage range: 0 to 24 V
Output current range: 0 to 50 mA.
Note that CME and COM are internally 
insulated, but are shorted externally by a 
jumper. In this case, DO1 is driven by +24 
V by default. Remove the jumper link if 
you need to apply external power to DO1.
FM COM High-speed pulse 
output
Controlled by F5-00 (FM terminal output 
selection).
Max. output frequency: 100 kHz.
When used as an open-collector output, 
the specication is the same as for DO1.
Relay 
outputs
T/A T/B Normally-closed 
(NC) terminal
Contact driving capacity:
250 VAC, 3 A, Cos f = 0.4
30 VDC, 1 A
Applies to overvoltage Category II circuit
T/A T/C Normally-open 
(NO) terminal
Auxiliary 
interfaces
J13 Extension card 
interface
Interface for the 28-core terminal and 
optional cards 
(I/O extension card, PLC card and various 
bus cards)
J4 PG card interface Open-collector, UVW and Resolver are 
selectable options.
J11 External 
operating panel 
interface
Connected to an external operating panel.
Jumpers
<2>
J7 AO1 output 
selection
Either a voltage or a current output, 
voltage output by default
J9 AI2 input 
selection
Either a voltage or a current input, voltage 
input by default.
J10 AI2 input 
impedance 
selection
Either 500 Ω or 250 Ω input, 500 Ω input 
by default
 ●
<1>
: Select 500 Ω or 250 Ω input impedance according to with-load capacity 
of signal source. For example, if 500 Ω is selected, maximum output 
voltage of signal source must not be smaller than 10 V so that AI2 can 
measure 20 mA current.
 ●