- 79 -
CONTINUE Para. Parameter name Default Commission
if it is SVC or FVC control
Adjust speed loop parameters  F2-00 Speed loop proportional gain 1 30
To achieve better performance
0 to 100.
F2-01 Speed loop integral time 1 0.5
0.01 to 10.00 Sec.
F2-02 Switchover frequency 1 5.00
0.00Hz to F2-05
F2-03 Speed loop proportional gain 2 20
0 to 100.
F2-04 Speed loop integral time 2 1.0
0.01 to 10.00 Sec.
F2-05 Switchover frequency 2 10.00
F2-02 to maximum output frequency
Finish