Options
‑97‑
Model
Dimensions (mm)
Mounting Hole (mm) Mounting
Hole
Diameter
(mm)
Weight
(kg)
H H1 W D A B
MD050‑T200G
983 1060 650 377 420 1030 12 130
MD050‑T220G
MD050‑T250G
MD050‑T280G
MD050‑T315G
1203 1358 800 400 520 1300 14 200
MD050‑T355G
MD050‑T400G
MD050‑T450G
Note
For installation and use of the energy feedback unit, see
MD051 Series Active Front End
(AFE) User Guide
.
5.4.7 Output Reactor
With an output reactor installed on the output side of the drive, the excessive dV/dt
can be reduced. This can lower the voltage stress on the motor winding to protect it,
lowers the motor temperature, and prolongs the service life of the motor.
Table 5–43 Minimum cable length with the output reactor configured (three phase 380–480
V)
AC Drive Power (kW) Rated Voltage (V) Min. Cable Length (m)
0.4–3.0 200–500 50
3.7 200–500 50
5.5 200–500 70
7.5 200–500 100
11 200–500 110
15 200–500 125
18.5 200–500 135
22 200–500 150
≥ 30
280–690 150
Table 5–44 Minimum cable length with the output reactor configured (three phase 200‑240
V)
AC Drive Power (kW) Rated Voltage (V) Min. Cable Length (m)
0.4–3 200–500 50
3.7 200–500 70