Commissioning and Trial Run
86
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F5‑01 62721 DO1/RO1 function
selection
0: No output
1: AC drive in running
2: Ready to run
3: Fault output 1 (stop
upon fault)
4: Fault output 2
5: Fault output 3
6: Abnormal output (direct
output upon fault or
alarm)
7: Motor overload pre‑
warning
8: AC drive overload pre‑
warning
9: Motor overtemperature
pre‑warning
10: AC drive load loss
output
11: Undervoltage state
output
12: Output current limit
exceeded
13: Frequency‑level
detection FDT1 output
14: Frequency‑level
detection FDT2 output
15: Frequency reached
16: Frequency 1 reached
output
17: Frequency 2 reached
output
18: Frequency upper limit
reached
19: Frequency lower limit
reached (output at stop)
20: Frequency lower limit
reached (no output at
stop)
21: Timing reached output
22: Accumulative power‑
on time reached
23: Accumulative running
time reached
24: Current running time
reached
3 Modifiable