Commissioning and Trial Run
‑98‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F9‑44 63788 Running time upon
1st fault
‑ Model
dependent
‑ Modification
prohibited
F9‑45 63789 IGBT temperature
upon 1st fault
‑ Model
dependent
‑ Modification
prohibited
F9‑46 63790 1st fault subcode ‑ Model
dependent
‑ Modification
prohibited
F9‑47 63791 Fault protection
action selection 0
Ones: Overcurrent at
constant speed or during
acceleration/deceleration
(E4/E2/E3)
0: Coast to stop
2: Restart upon fault
Tens: Overvoltage at
constant speed or during
acceleration/deceleration
(E7/E5/E6)
0: Coast to stop
2: Restart upon fault
Hundreds: Reserved
5: Cancel
Thousands: Undervoltage
(E9)
0: Coast to stop
2: Restart upon fault
Ten thousands: AC drive
overload (E10)
0: Coast to stop
2: Restart upon fault
500 ‑ Modifiable
only at stop