Commissioning and Trial Run
‑99‑
Parameter
No.
Communication
Address
Parameter Name Setting Range Default Unit Property
F9‑48 63792 Fault protection
action selection 1
Ones: Motor overload
(E11)
0: Coast to sop
1: Decelerate to stop
2: Restart upon fault
4: Warning
5: Cancel
Tens: Reserved
0: Coast to sop
1: Decelerate to stop
4: Warning
5: Cancel
Hundreds: Output phase
loss (E13)
0: Coast to sop
1: Decelerate to stop
2: Reset upon fault
4: Warning
5: Cancel
Thousands: IGBT
overtemperature (E14)
0: Coast to sop
Ten thousands: External
device fault (E15)
0: Coast to sop
1: Decelerate to stop
4: Warning
5: Cancel
10050 Modifiable
only at stop
F9‑49 63793 Fault protection
action selection 2
Ones: Communication
fault (E16)
0: Coast to stop
1: Decelerate to stop
4: Warning
5: Cancel
Tens: Reserved
5: Cancel
Hundreds: Reserved
0: Coast to stop
Thousands: Motor auto‑
tuning fault (E19)
0: Coast to stop
4: Warning
5: Cancel
Ten thousands: Reserved
5: Cancel
50050 Modifiable
only at stop