- 93 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
Example:
If oors 2, 8, 9, and 12 of a 16-oor elevator need to be forbidden, and all other oors are in service, we need to
set Bit1, Bit7, Bit8, and Bit11 corresponding to oors 2, 8, 9, and 12 to 0, and set the other bits to 1, as shown in
the following gure.
1
0
4
8
16
32
64
0
0
512
1024
0
4096
8192
16384
32768
Bit2 = 1
Bit1 = 0
Bit3 = 1
Bit4 = 1
Bit5 = 1
Bit6 = 1
Bit7 = 0
Bit8 = 0
Bit9 = 1
Bit10 = 1
Bit11 = 0
Bit12 = 1
Bit13 = 1
Bit14 = 1
Bit15 = 1
Bit0Bit11
Bit1Bit2Bit3Bit4
Bit5Bit6Bit7
Bit8Bit9Bit10Bit12Bit13
Bit14
Bit15
1612
248
1632
64128256
10242048
4096
8192
Bit Addressing
Binary Addressing
16384
32768
Floor 1
Floor 2
Floor 3
Floor 4
Floor 5
Floor 6
Floor 7
Floor 8
Floor 9
Floor 10
Floor 11
Floor 12
Floor 13
Floor 14
Floor 15
Floor 16
Bit0 = 1
Forbidden
Forbidden
Forbidden
Forbidden
Convert the binary value to decimal:
1 + 4 + 8 + 16 + 32 + 64 + 512 + 1024 + 4096 + 8192 + 16384 + 32768 = 63101
Then, enter ā€œ63101ā€ for F6-05 on the operation panel.
F6-07
Number of elevators in
parallel/group mode
1 to 8 1 -
ā˜…
F6-08 Elevator No. 1 to 8 1 -
ā˜…
F6-09 Elevator program control
Bit0: Dispersed waiting
Bit2: Reserved
Bit3: Parallel/Group control
implemented at CAN2
Bit4: Group control in compatibility
with NICE3000
Bit6: Clear oor number and
display direction in advance
Bit8: Unidirectional hall call (single
hall call button)
Bit 9: Not detecting analog wire
breaking
Bit10: Cancellation of ERR30
judgment at re-leveling
Bit14: Time interval detection
of safety circuit 2 and door lock
circuit 2 (1.5s)
0 -
ā˜…