P/N 422-6367-ML • REV E • ISS 03DEC18    3 / 14 
•  Clear “line-of-sight” between the “microphone” of the 
detector and the glass is required. 
•  Detector location for wall or ceiling mount is shown in 
Figure 10. 
- Distance between the glass and the detector should be 1 
to 9 m. 
- Detector should be installed min. 50 cm from a corner. 
- Detector should be installed min. 1 m over the floor. 
- Detector should be installed min. 30 cm from the ceiling 
(at wall mounting). 
•  Detector should be installed on a flat surface, which is free 
from objects in a radius of 50 cm from the detector. 
•  Detector should not be installed close to air vents or big 
sound reflecting obstacles. 
•  Never mount the detector in the corners. 
Installation 
1.  Choose the best mounting position on the wall or ceiling. 
2.  Loosen the cover screw and remove the upper part  
3.  Use the bottom part as a template and mark the place of 
the holes of with a pen 
4.  Use a 2.5 mm drill for the self-tapping screws provided. If 
necessary, use wall anchors 
5.  If necessary, cut out the marked “knockout hole” on the 
back of the base with a pair of tongs 
6.  Pull the wiring cable through the “knockout hole” in the 
bottom plate 
7.  Connect the wires to the screw terminals. See Table 1 
below for information. 
8.  Use the cable strap provided to fix the wiring cable to the 
detector. 
9.  Fix the detector firmly to the base with the enclosed 
screws. 
10.  Set the desired range, i.e. the detector sensitivity setting 
by using the DIP switch no 2 and 3. See “DIP switch” 
below for details. 
11.  Check the window constructions and note what kind of 
glass is used and especially in the pane closest to the 
room. 
Table 1: Terminal pins 
Day and Night control of LED 
INTRUSION relay output NC 
Spare contact (unconnected) 
Spare contact (unconnected) 
Spare contact (unconnected) 
Spare contact (unconnected) 
Spare contact (unconnected) 
Note: You can use the additional accessory GS960-RB plug-in 
EOL resistor board, which allows you to easily integrate GS960 
into an existing Advisor Advanced system without the hassle of 
adding EOL resistors. 
DIP switch 
DIP switch functions are described in Table 2 below. 
Table 2: DIP switch functions 
INTRUSION relay mode 
•  DIP 1 ON: INTRUSION relay mode ON means the 
INTRUSION relay will Latch and be open in alarm.  
•  DIP 1 OFF: INTRUSION relay mode OFF means the 
INTRUSION relay will be auto reset after 2 seconds in 
alarm. 
Range 
DIP switch range settings are shown in Figure 6. 
Figure 6: DIP switch range settings 
(1)  4 to 9 m, Zone 1: OFF, OFF 
(2)  2 to 4 m, Zone 2: OFF, ON, or ON, OFF 
(3)  1 to 2 m, Zone 3: ON, ON 
Suggested settings of the detector 
depending on window design and type of 
glass 
Check the window constructions and note what kind of glass is 
used and especially in the pane closest to the room. 
•  Single glazed (float & tempered) – Set the detector at the 
measured distance from the glass to the detector. 
•  Double glazed (float & tempered). If there are high 
disturbances in the surroundings – set the detector at the 
measured distance from the glass to the detector. At 
normal or low disturbances – the detector shall be set at 
Zone 1. 
•  Double glazed where the inner pane is covered with 
security film – Set the detector at Zone 1 apart from the 
measured distance. 
•  Triple glazed (float & tempered) – Set the detector at 
Zone 1 apart from measured distance. 
•  Laminated glass – Set the detector at Zone 1 apart from 
the measured distance.