Version 1.00 | Optidrive CoolVert User Guide | 35www.invertekdrives.com
4
Set-up and Operation
4.4.3. Group 3 Parameters & Modbus Registers
Par
Mod
Add Description Def Min Max Unit R/W
3-01 301 Skip Speed 1 Centre Point 0.0 0.0 500 rps R/W
Defines the centre point of skip frequency 1 band. The width of the skip frequency band is defined by:
Lower Limit = P3-01 – P3-02/2
Upper Limit = P3-01 + P3-02/2
3-02 302 Skip Speed 1 Bandwidth 0.0 0.0 5.0 rps R/W
The width of skip frequency 1 band is defined by:
Lower Limit = P3-01 – P3-02/2
Upper Limit = P3-01 + P3-02/2
3-03 303 Skip Speed 2 Centre Point 0.0 0.0 500 rps R/W
Defines the centre point of skip frequency 2 band. The width of the skip frequency band is defined by:
Lower Limit = P3-03 – P3-04/2
Upper Limit = P3-03 + P3-04/2
3-04 304 Skip Speed 2 Bandwidth 0.0 0.0 5.0 rps R/W
The width of skip frequency 2 band is defined by:
Lower Limit = P3-03 – P3-04/2
Upper Limit = P3-03 + P3-04/2
3-05 305 User Relay Output Function Select 1 0 12 - R/W
0: Drive Running
1: Drive Healthy (Not Tripped)
2: Drive Tripped
3: At Speed
4: Speed >0
5: STO Status
6: Fieldbus control (control word)
7: Motor speed > P3-06 (off when < P3-07)
8: Motor current > P3-06 (off when < P3-07)
9: Analogue Input > P3-06 (off when < P3-07)
10: PI error > P3-06 (off when < P3-07)
11: Loss of analogue input signal
12: Loss of serial communication
3-06 306 User Relay Function Upper Limit 100 P3-07 200 % R/W
Sets the upper limit for the relay control when P3-05 is set to a value between 7 - 10.
3-07 307 User Relay Function Lower Limit 0.0 0.0 P3-06 % R/W
Sets the lower limit for the relay control when P3-05 is set to a value between 7 - 10.
3-08 308
Slave Speed Scaling Control (Set in the Master)
0 0 1 - R/W
0: No Scaling
1: Slave Speed = Master Speed x P3-09
3-09 309
Slave Speed Scaling Factor (Set in the Master)
100 -500 +500 % R/W
0: Disabled
1: Slave Speed = Master Speed x P3-09
3-10 310 Analogue Input Format 0 0 8 - R/W
0: 0-10V
1: 10-0V
2: t4-20mA (trip on signal loss)
3: t20-4mA (trip on signal loss)
4:
p4-20mA (run at P3-11 speed on signal loss)
5: p20-4mA (run at P3-11 speed on
signal loss)
6: 0-20mA
7: 20-0mA
8: PTC (Motor Thermistor Trip)
3-11 311 Signal Loss Run Speed 30 P1-02 P1-01 Rps R/W
Defines the speed at which the drive will run at in the event of a loss of analogue signal if P3-10 is set equal to 5 or 6,
or in the event of loss of serial communications if P1-11 is set to 0 (Modbus control) and P6-05 is set to 3.
3-12 312 Analogue Input Scaling 100 0.0 2000 % R/W
Output Value = (Input Value – Offset) x Scaling
3-13 313 Analogue Input Offset 0 -500 +500 % R/W