EasyManua.ls Logo

Invertek OPTIDRIVE Coolvert - Page 43

Invertek OPTIDRIVE Coolvert
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Version 1.00 | Optidrive CoolVert User Guide | 43www.invertekdrives.com
6
Technical Data
Control Specification
Output Voltage 0 - Vin
PWM Frequency 4 – 32kHz
Stop Mode Ramp to stop, Ramp to minimum speed then coast to stop, Coast to stop
Skip Frequency 2 skip frequencies, user adjustable
Control Modes Modbus RTU (RS485)
Terminal Control Digital / Analogue
Terminal Control PI mode
Master / Slave Mode
I/O Specification
Power Supply 24 Volt DC, 100mA, Short Circuit Protected
Digital Inputs 1 (24V Positive Logic)
Analogue Inputs 1 (0-10V, 0-20mA, 4-20mA, PTC)
Relay Outputs 1 (AB type)
Maximum Voltage 250VAC, 30VDC
Switching Current Capacity: 6A AC, 5A DC
Resistive Load
Safe Torque Off (STO) Independently approved STO input
Safe Torque Off (STO)
IEC 61800-5-2:2016 SIL 3
EN ISO 13849-1:2015 PL “e”
EN 61508 (Part 1 to 7): 2010 SIL 3
EN 60204-1: 2006 & A1: 2009 Cat 0
EN 62061: 2005 & A2: 2015 SIL CL 3
Application Features
PI Control Internal PI Controller.
3 - step start-up profile Start-up profile configurable with up to 3-steps to reduce the risk of oil migration and
support better charge distribution in the system.
Compressor start-up protection Several configurable built-in compressor protection features including Minimum
Compressor On Time, Minimum Compressor Off Time and Compressor Restart Delay.
Intelligent Drive Thermal
Management
Reduced-load operation of the compressor can be configured under high drive
temperatures to prevent nuisance tripping.
Intelligent Motor Thermal
Management
Reduced-load operation of the compressor can be configured under continued motor
overload to prevent nuisance tripping.
Serial Communications-Loss Fall-
Back Speed
The ability to configure the drive to run at a ‘safe’ speed in the event of a loss of serial
communication. Can prevent loss of cooling/heating.
Master Follower Configuration The ability to run a cascade of compressors with one Master regulating the operating point
in PI Control.
Maintenance & Diagnostics
Fault Memory Last 3 trips stored with time stamp
Data Logging Logging of data prior to last trip for diagnostic purposes:
Output Current
Drive Temperature
DC Bus Voltage.
Monitoring Hours Run Meter
kWH

Related product manuals