BPD series PV pumping inverter Function parameters
26
Function
code
Name
Detailed description
Default
Modify
Note:
1. The function code will restore to 0 after finishing
the operation of the selected function code.
2. Restoring to the default value will cancel the
user password, please use this function with
caution.
P01 Group Start-up and stop control
P01.08
Stop mode
0: Decelerate to stop: after the stop command
becomes valid, the inverter decelerates to reduce
the output frequency during the set time. When the
frequency decreases to 0Hz, the inverter stops.
1: Coast to stop: after the stop command becomes
valid, the inverter ceases the output immediately.
And the load coasts to stop at the mechanical
inertia.
0
P01.18
Operation
protection
0: The terminal running command is invalid when
powering on.
1: The terminal running command is valid when
powering on.
1
P01.21
Restart after
power off
0: Disabled
1: Enabled
1
P02 Group Motor 1 parameters
P02.00
Motor type
0: 3PH motor
1: 1PH motor
Depend
on
mode
P02.01
Rated power
of
asynchronous
motor
0.13000.0kW
Set the parameter of the
asynchronous motor.
In order to ensure the
controlling performance,
set the P02.01P02.05
according to the name
plate of the
asynchronous motor.
Pump inverters provide
Depend
on
model
P02.02
Rated
frequency of
asynchronous
motor
0.01HzP00.03
50.00Hz
P02.03
Rated speed
136000rpm
Depend