When A and B frequency commands are
selected as “keypad setting”, this parameter will
be the initial value of VFD reference frequency
Setting range: 0.00Hz–P00.03 (max. output
frequency)
ACC time means the time needed if the VFD
speeds up from 0Hz to max. output frequency
(P00.03).
DEC time means the time needed if the VFD
speeds down from max. output frequency to 0Hz
(P00.03).
Goodrive10 series VFDs define four groups of
ACC/DEC time which can be selected by P05.
The factory default ACC/DEC time of the VFD is
the first group.
Setting range of P00.11 and P00.12:
0.0–3600.0s
0: Runs at the default direction, the VFD runs in
the forward direction. FWD/REV indicator is off.
1: Runs at the opposite direction, the VFD runs
in the reverse direction. FWD/REV indicator is
on.
Modify the function code to shift the rotation
direction of the motor. This effect equals to the
shifting the rotation direction by adjusting either
two of the motor lines (U, V and W). The motor
rotation direction can be changed by
QUICK/JOG on the keypad. Refer to parameter
P07.02.
Note: When the function parameter comes back
to the default value, the motor’s running
direction will come back to the factory default
state, too. In some cases it should be used with
caution after commissioning if the change of
rotation direction is disabled.
2: Forbid to run in reverse direction: It can be
used in some special cases if the reverse
running is disabled.