Goodrive100-PV Series Solar Pumping VFD   Function parameters 
48 
Detailed illustration of parameters 
Wake-up delay in 
full water state 
0–10000s 
Time  setting  of  wake-up  delay  in 
full-water  state  (This  function  code  is 
still  valid  when  the digital  indicates  the 
full-water signal.) 
0–10000s 
Time setting of empty-water delay (This 
function  code  is  still  valid  when  the 
digital indicates the empty-water signal.) 
Wake-up delay in 
empty-water state 
0–10000s 
Time  setting  of  wake-up  delay  in 
empty-water state (This function code is 
still  valid  when  the digital  indicates  the 
empty-water signal.) 
0.0–100.0% 
0.0%: Invalid. If it is not 0.0%, when the 
signal  is  longer  than  P15.18,  it  will 
report tSF fault directly and stop. 
Operation time of 
water pump 
underload 
0.0–1000.0s 
This  parameter  is  used  to  set  the 
operation  time  of  water  pump 
underload.  Under  the  continuous 
underload  operation,  underload 
prealarm  (A-LL)  will  be  reported  if  the 
operation time is reached. 
Current detection 
value of underload 
operation 
0.0%: Automatic underload detection 
0.1–100.0% 
If  it  is  0.0%,  it  is  determined  by  the