Goodrive300 Series VFD    Technical data 
247 
altitude on the site is higher than 1000 m, and not more than 3000 m, the maximum power is derated 
by 1% for every increased 100 m. For details about the derating, see the following figure. 
Derating coefficient (%) 
Altitude (m)
100
80
60
40
20
0
1000 2000 3000 4000
 
When the altitude exceeds 2000m, configure an isolation transformer on the input end of the VFD. 
When the altitude exceeds 3000m but is lower than 5000m, contact us for technical consultation. Do 
not use the VFD at an altitude higher than 5000m. 
B.2.2.3 Carrier frequency derating   
For Goodrive300 series VFDs, different power level corresponds to different carrier frequency range. 
The rated power of the VFD is based on the factory carrier frequency, so if it is above the factory 
value, the VFD needs to derate 10% for every additional 1 kHz carrier frequency. 
B.3 Grid specifications 
AC 3PH 380V(-15%)–440V(+10%)   
AC 3PH 380V(-10%)–550V(+10%) 
AC 3PH 520V(-15%)–690V(+10%) 
Maximum allowed prospective short-circuit current at the input power 
connection as defined in IEC 60439-1 is 100 kA. The drive is suitable 
for use in a circuit capable of delivering not more than 100 kA at the 
drive maximum rated voltage.   
50/60 Hz ± 5%, maximum rate of change 20%/s 
B.4 Motor connection data   
Asynchronous  induction  motor  or  synchronous  permanent  magnet 
motor 
0 to U1, 3-phase symmetrical, Umax at the field weakening point 
The motor output is short-circuit proof by IEC 61800-5-1 
Refer to section 3.6 "Rated specifications"