EasyManuals Logo

INVT GD300-037G-4 User Manual

INVT GD300-037G-4
289 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #154 background imageLoading...
Page #154 background image
Goodrive300 Series VFD Basic operation instruction
149
2. The starting logic figure of starting after the restarting function becomes valid during the normal
powering on.
Standby
Operation status
before power outage
0
1
P01.21
(Enable/disable restart
after power outage)
Waiting time of restart
after power
outage>P01.22
0
1
2
Stop
Run
0
1
P01.18
(Terminal running protection when powering on)
Restart delay time
>P01.23
N
Y
Y
N
Restart after
power outage
Run
Stop
Whether the FWD/REV
terminal running command is
valid
N
Run
Y
P00.01
Running command
channel
Keypad
Communication
Terminal
3. The starting logic figure of starting after the automatic fault reset.
VFD fault occurs
In running
Number of automatic
fault reset times of the
VFD<P08.28
Interval time of automatic
fault reset of the
VFD>P08.29
The VFD resets
after the fault and
starts to run.
The fault code is
displayed and the
VFD stops.
N
N
Y
Y
Related parameters
Function
code
Name
Detailed instruction of parameters
Default
value
P00.01
Running command
channel
0: Keypad
1: Terminal ("LOCAL/REMOT" flickering)
2: Communication ("LOCAL/REMOT"
on)
0
P00.11
ACC time 1
0.03600.0s
Depend
on model

Table of Contents