Goodrive300 Series VFD Basic operation instruction
137
Function
code
Name
Description
Default
value
frequency 1 of motor 1
P04.04
V/F
voltage 1 of motor 1
0.0%110.0%
0.0%
P04.05
V/F
frequency 2 of motor 1
P04.03 P04.07
00.00Hz
P04.06
V/F
voltage 2 of motor 1
0.0%110.0%
0.0%
P04.07
V/F
frequency 3 of motor 1
P04.05P02.02 or P04.05P02.16
00.00Hz
P04.08
V/F
voltage 3 of motor 1
0.0%110.0%
0.0%
P04.09
V/F slip compensation
gain of motor 1
0.0200.0%
100.0%
P04.10
Vibration control factor at
low frequency of motor 1
0100
10
P04.11
Vibration control factor at
high frequency of motor 1
0100
10
P04.12
Vibration control threshold
of motor 1
0.00HzP00.03 (Max. output frequency)
30.00 Hz
P04.13
Motor 2 V/F curve setting
0: Straight line V/F curveapplying to the
constant torque load
1: Multi-dots V/F curve
2: 1.3
th
power low torque V/F curve
3: 1.7
th
power low torque V/F curve
4: 2.0
th
power low torque V/F curve
5: Customized V/F (V/F separation)
0
P04.14
Torque boost of motor 2
0.0%: (automatic) 0.1%10.0%
0.0%
P04.15
Torque boost close of
motor 2
0.0%50.0% (rated frequency of motor 1)
20.0%
P04.16
V/F
frequency 1 of motor 2
0.00HzP04.05
0.00Hz
P04.17
V/F
voltage 1 of motor 2
0.0%110.0%
0.0%
P04.18
V/F
frequency 2 of motor 2
P04.16 P04.20
0.00Hz
P04.19
V/F
voltage 2 of motor 2
0.0%110.0%
0.0%