Goodrive300 Series VFD Basic operation instruction
151
Function
code
Name
Detailed instruction of parameters
Default
value
valid when powering on
P01.19
Action if running
frequency<lower limit
frequency
(valid when lower limit>0)
0: Run at the lower-limit frequency
1: Stop
2: Hibernation
0
P01.20
Hibernation restore delay
time
0.03600.0s (valid when P01.19=2)
0.0s
P01.21
Restart after power
outage
0: Disable
1: Enable
0
P01.22
Waiting time of restart
after power outage
0.03600.0s (valid when P01.21=1)
1.0s
P01.23
Start delay time
0.060.0s
0.0s
P01.24
Delay time of the stop
speed
0.0100.0s
0.0s
P05.01P05
.09
Digital input function
selection
1: Forward rotation operation
2: Reverse rotation operation
4: Forward rotation jogging
5: Reverse rotation jogging
6: Coast to stop
7: Fault reset
8: Operation pause
21: ACC/DEC time option
22: ACC/DEC time option
30: ACC/DEC prohibition
P08.06
Jogging frequency
0.00HzP00.03 (Max. frequency)
5.00Hz
P08.07
Jogging ACC time
0.03600.0s
Depend
on model
P08.08
Jogging DEC time
0.03600.0s
Depend
on model
P08.00
ACC time 2
0.03600.0s
Depend
on model
P08.01
DEC time 2
0.03600.0s
Depend
on model
P08.02
ACC time 3
0.03600.0s
Depend
on model
P08.03
DEC time 3
0.03600.0s
Depend
on model