Goodrive300 Series VFD    Extension card 
238 
EC-TX-103  communication  cards).  In  order  to  use  PROFIBUS/CANOPEN  control  VFD,  the 
communication module must be set to be VFD controller.   
Actual value: Actual value is a 16-bit word, which contains converter operation information. Monitoring 
capabilities  are  defined  by  VFD  parameter.  The  integer  scaling  of  actual value  is  sent  to  master 
machine depending on selected function, please refer to VFD manual.   
Note: VFD always check the control word (CW) and bytes of given value.   
Mission message (From master station to VFD)   
Control word (CW): The first word of PZD is control word (CW) of VFD. The definitions of CWs on the 
PWM rectifier regenerative part are different from those on the inverter part, and therefore two tables 
are used to describe the CWs. 
Control word (CW) of Goodrive300 series 
Coast to stop (Emergency stop) 
Write enable (mainly is PKW1-PKW4 ) 
ELECTRIC CONSUMPTION 
CLEAR 
Electric consumption clear enable 
Electric consumption clear disable