Goodrive300 Series VFD    Function parameters 
48 
Detailed instruction of parameters 
VFD because of the bus voltage fluctuation. 
Function 
restore 
parameter 
0: No operation   
1: Restore the default value 
2: Cancel the fault record   
Note:  The  function  code  will  restore  to  0  after 
finishing  the  operation  of  the  selected  function 
code. 
Restoring to the default value will cancel the user 
password, please use this function with caution. 
P01 Group    Start-up and stop control 
0:  Start-up  directly:start  from  the  starting 
frequency P01.01   
1: Start-up after DC braking: start the motor from 
the  starting  frequency  after  DC braking (set  the 
parameter  P01.03  and  P01.04).  It  is  suitable  in 
the  cases  where  reverse  rotation  may  occur  to 
the low inertia load during starting. 
2: Start-up  after speed tracing: start the  rotating 
motor smoothly after tracking  the rotation speed 
and  direction  automatically.  It  is  suitable  in  the 
cases where reverse rotation may occur to the big 
inertia load during starting.   
Note: This function is provided for VFDs of 4kW 
or above. 
Starting 
frequency of 
direct start 
Starting  frequency  of  direct  start-up  means  the 
original  frequency  during  the  VFD  starting.  See 
P01.02 for detailed information. 
Setting range: 0.00–50.00Hz 
Retention time 
of the starting 
frequency 
Set  a  proper  starting  frequency  to  increase  the 
torque  of  the  VFD  during  starting.  During  the 
retention time of the starting frequency, the output 
frequency  of  the  VFD  is  the  starting  frequency. 
And  then,  the  VFD  will  run  from  the  starting 
frequency  to  the  set  frequency.  If  the  set 
frequency is lower than the starting frequency, the 
VFD  will  stop  running and keep  in  the  stand-by