Goodrive300 Series VFD Function parameters
67
Detailed instruction of parameters
Vibration
control factor
at low
frequency of
motor 1
In SVPWM control mode, current fluctuation may
occur to the motor at some frequency, especially
the motor with big power. The motor cannot run
stably or overcurrent may occur. These
phenomena can be canceled by adjusting this
parameter.
Setting range of P04.10: 0–100
Setting range of P04.11: 0–100
Setting range of P04.12: 0.00Hz–P00.03 (Max.
frequency)
Vibration
control factor
at high
frequency of
motor 1
Vibration
control
threshold of
motor 1
Motor 2 V/F
curve setting
This group of parameters defines the V/F setting
modes of Goodrive300 motor 2 to meet various
requirements of different loads. See
P04.00–P04.12 for the detailed function code
instruction.
Note: P04 group includess two sets of V/F
parameters of the motor which cannot display
simultaneously. Only the selected V/F parameter
can be shown. The motor selection can be
defined by terminals function "the shift between
motor 1 and motor 2".
Torque boost
close of motor
2
V/F
frequency 1 of
motor 2
V/F
frequency 2 of
motor 2
V/F
frequency 3 of
motor 2