Goodrive300 Series VFD Function parameters
68
Detailed instruction of parameters
V/F slip
compensation
gain of motor
2
Vibration
control factor
at low
frequency of
motor 2
In SVPWM control mode, current fluctuation may
occur to the motor on some frequency, especially
the motor with big power. The motor cannot run
stably or overcurrent may occur. These
phenomena can be canceled by adjusting this
parameter.
Setting range of P04.23: 0–100
Setting range of P04.24: 0–100
Setting range of P04.25: 0.00 Hz–P00.03 (Max.
output frequency)
Vibration
control factor
at high
frequency of
motor 2
Vibration
control
threshold of
motor 2
0: No operation
1: Automatic energy-saving operation
Motors with light load will automatically adjust the
output voltage to save energy.
Select the output setting channel at V/F curve
separation.
0: Keypad: the output voltage is determined by
P04.28.
1: AI1
2: AI2
3: AI3
4: HDI
5: Multi-step speed
6: PID
7: Modbus communication
8: PROFIBUS/CANopen communication
9: Ethernet communication