Goodrive300 Series VFD Function parameters
69
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
10: Reserved
Note: 100% corresponds to the rated voltage of
the motor.
P04.28
Keypad
setting voltage
The function code is the voltage displaying when
the voltage is set through keypad.
Setting range: 0.0%100.0%
100.0%
P04.29
Voltage
increasing
time
Voltage increasing time is the time when the VFD
accelerates from the output minimum voltage to
the output maximum voltage.
Voltage decreasing time is the time when the VFD
decelerates from the output maximum voltage to
the output minimum voltage.
Setting range: 0.03600.0s
5.0s
P04.30
Voltage
decreasing
time
5.0s
P04.31
Max. output
voltage
Set the upper and low limit of the output voltage.
Vmax
Vmin
Vset
t1 t2
Time
t1=P04.29
t2=P04.30
Setting range of P04.31: P04.32100.0%(the
rated voltage of the motor)
Setting range of P04.32: 0.0% P04.31(the rated
voltage of the motor)
100.0%
P04.32
Min. output
voltage
0.0%
P04.33
Weaking
coefficient at
constant
power
Used during field-weakening operation to adjust
the output voltage of VFD in SVPWM mode.
Note: Invalid in constant-torque mode.
Output Voltage
Output frequency
V
out
V
b
f
b
2f
b
(P04.33-1.00) x V
b
Setting range of P04.33: 1.001.30
1.00
P05 Group Input terminals
P05.00
HDI input
selection
0: High pulse input. See P05.49P05.54
1: Digital input. See P05.09.
0