Goodrive300 Series VFD Function parameters
70
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P05.01
S1 terminals
function
selection
0: No function
1: Forward rotation operation
2: Reverse rotation operation
3: 3-wire control operation
4: Forward jogging
5: Reverse jogging
6: Coast to stop
7: Fault reset
8: Operation pause
9: External fault input
10: Increasing frequency setting(UP)
11: Decreasing frequency setting(DOWN)
12: Frequency setting clear
13: Shift between A setting and B setting
14: Shift between combination setting and A
setting
15: Shift between combination setting and B
setting
16: Multi-step speed terminal 1
17: Multi-step speed terminal 2
18: Multi-step speed terminal 3
19: Multi- step speed terminal 4
20: Multi- step speed pause
21: ACC/DEC time 1
22: ACC/DEC time 2
23: Simple PLC stop reset
24: Simple PLC pause
25: PID control pause
26: Traverse Pause (stop at the current
frequency)
27: Traverse reset (return to the center
frequency)
28: Counter reset
29: Torque control disabling
30: ACC/DEC disabling
31: Counter trigging
32: Length reset
33: Cancel the frequency change setting
1
P05.02
S2 terminals
function
selection
4
P05.03
S3 terminals
function
selection
7
P05.04
S4 terminals
function
selection
0
P05.05
S5 terminals
function
selection
0
P05.06
S6 terminals
function
selection
0
P05.07
S7 terminals
function
selection
0
P05.08
S8 terminals
function
selection
0
P05.09
HDI terminal
function
selection
0