Goodrive300 Series VFD    Function parameters 
108 
Detailed instruction of parameters 
LED tens: 
0:  The  VFD  continues  to  work  after  underload 
pre-alarm   
1:  The  VFD  continues  to  work  after  underload 
pre-alarm and the VFD stops to run after overload 
fault   
2:  The  VFD  continues  to  work  after  overload 
pre-alarm  and  the  VFD  stops  to  run  after 
underload fault 
LED hundreds : 
0: Detection all the time 
1: Detection in constant running 
Setting range of P11.09: P11.11–200% 
Setting range of P11.10: 0.1–3600.0s 
Underload 
pre-alarm 
detection 
If the VFD current or the output current is lower 
than  P11.11,  and  its  lasting  time  is  beyond 
P11.12, the VFD will output underload pre-alarm.   
Setting range of P11.11: 0–P11.09 
Setting range of P11.12: 0.1–3600.0s 
Underload 
pre-alarm 
detection time 
Output 
terminal action 
during fault   
Select  the  action  of  fault  output  terminals  on 
undervoltage and fault reset. 
0x00–0x11 
LED ones: 
0: Action under fault undervoltage 
1: No action under fault undervoltage 
LED tens: 
0: Action during the automatic reset   
1: No action during the automatic reset 
Speed 
deviation 
detection     
0.0–50.0% 
Set the speed deviation detection time. 
Speed 
deviation 
detection time   
This parameter is used to see the speed deviation 
detection time.