Goodrive300 Series VFD Function parameters
115
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
source current
P13.01
Original pole
test mode
0: No test
1: High-frequency superposition (reserved)
2: Pulse superposition
0
P13.02
Source current
1
Source current is the positioning current of the
magnetic pole position. Source current 1 is valid
under the frequency point of current shifting.
Increasing the value can raise the starting torque.
Setting range: 0.0%100.0% (rated current of the
motor)
20.0%
P13.03
Source current
2
Source current is directional current of the
magnetic pole position. Source current 2 is valid
under the frequency point of current shifting.
There is no need to modify the value generally.
Setting range: 0.0%100.0% (rated current of the
motor)
10.0%
P13.04
Shift
frequency of
source current
Valid frequency shifting point between source
current 1 and current 2.
Setting range: 0.00HzP00.03 (Max. frequency)
10.00
Hz
P13.05
Superposing
frequency
(reserved)
2001000Hz
500Hz
P13.06
Pulse
superposing
voltage
0.0300.0% (rated voltage of the motor)
40.0%
P13.07
Reserved
065535
0
P13.08
Control
parameter 1
065535
0
P13.09
Control
parameter 2
0655.35
2.00
P13.10
Reserved
065535
0
P13.11
Maladjustment
detection time
Adjust the response of anti-maladjustment.
Bigger load inertia may increase the value, but
the response will be slower.
Setting range: 0.010.0s
0.5s
P13.12
High
frequency
When the motor speed is faster than the rated
speed, the parameter is valid, if vibration occurs
0.0%