Detailed instruction of parameters
to the motor, please adjust the parameter.
Setting range: 0–100.0%
Braking
current of
short-circuit
When P01.00=0 during the starting of the VFD,
set P13.14 to a non-zero value to enter the short
circuit braking.
When the running frequency is lower than P01.09
during the stopping of the VFD, set 13.15 to a
non-zero value to enter into stopping short
circuited braking and then carry out the DC
braking at the time set by P01.12 (refer to the
instruction of P01.09–P01.12) .
Setting range of P13.13: 0.0–150.0% (the VFD)
Setting range of P13.14: 0.00–50.00s
Setting range of P13.15: 0.00–50.00s
Braking
retention time
before
starting
The braking
retention time
when stopping
P14 Group Serial communication
Local
communicatio
n address
Setting range:1–247
When the master is writing the frame, the
communication address of the slave is set to 0;
the address is the communication address. All
slaves on the Modbus fieldbus can receive the
frame, but the salve doesn’t answer.
The communication of the drive is unique in the
communication net. This is the fundamental for
the point to point communication between the
upper monitor and the drive.
Note: The address of the slave cannot set to 0.
Set the digital transmission speed between the
upper monitor and the VFD.
0: 1200BPS
1: 2400BPS
2: 4800BPS
3: 9600BPS
4: 19200BPS
5: 38400BPS
6: 57600BPS
7: 115200BPS
Note: The baud rate between the upper PC and