Goodrive300 Series VFD Function parameters
93
Detailed instruction of parameters
0: Disabled
1: Enabled
0x00–0x14
FDT1
electrical level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level,
the multi-function digital output terminals will
output the signal of "frequency level detect FDT"
until the output frequency decreases to a value
lower than (FDT electrical level—FDT retention
detection value) the corresponding frequency, the
signal is invalid. Below is the ware form diagram:
Output frequency
FDT electrical level
FDT retention
Time
Time
Y, RO1, RO2
Setting range of P08.32: 0.00Hz–P00.03 (Max.
frequency)
Setting range of P08.33: 0.0–100.0% (FDT1
electrical level)
Setting range of P08.34: 0.00Hz–P00.03 (Max.
frequency)
Setting range of P08.35: 0.0–100.0% (FDT2
electrical level)
FDT1
retention
detection
value
FDT2
electrical level
detection
value
FDT2
retention
detection
value
Frequency
arrival
detection
range
When the output frequency is among the positive
or negative detection range of the set frequency,
the multi-function digital output terminal will
output the signal of "frequency arrival", see the
diagram below for detailed information: