Goodrive300 Series VFD Function parameters
94
Detailed instruction of parameters
Y
RO1, RO2
,
Output frequency
Set frequency
Detectionn range
Time
Time
Setting range: 0.00Hz–P00.03 (Max. frequency)
This parameter is used to control the enabling of
the internal braking pipe inside the VFD.
0: Disable
1: Enable
Note: This function is only applicable to the
internal braking pipe.
Dynamic
braking
threshold
voltage
Set the initial bus voltage for dynamic braking.
This value can be adjusted to perform valid
braking on a load. The factory setting changes
with the voltage class.
Setting range: 200.0–2000.0V
To prevent customers from setting a value that is
too large, the following setting ranges are
recommended:
0: Normal mode
1: The fan keeps running after being powered on.
0x00–0x21
LED ones: PWM mode selection
0: PWM mode 1, three-phase modulation and
two-modulation
1: PWM mode 2, three-phase modulation
LED tens: low-speed carrier frequency limit mode
0: Low-speed carrier frequency limit mode 1, the
carrier frequency will limit to 2k if it exceeds 2k at
low speed
1: Low-speed carrier frequency limit mode 2, the