Goodrive35 Series Closed-loop Vector Control VFD  Function parameters 
89 
Detailed instruction of parameters 
P08 Group Enhanced function   
For detailed definition, see the description of P00.11 
and P00.12. 
Four groups of ACC and DEC time are defined for 
the  Goodrive35  series.  You  can  set  the  ACC  and 
DEC  time  through the  corresponding multi-function 
digital  input  terminals  (in  the  P05  group).  For  the 
Goodrive35 series VFD, the default setting is the first 
group of ACC and DEC time. 
Setting range: 0.0–3600.0s 
This  parameter  is  used  to  set  the  reference 
frequency of the VFD during jogging.   
Setting  range:  0.00  Hz–P00.03  (max.  output 
frequency) 
P08.07  indicates  the  time  the  VFD  takes  to 
accelerate  from  0  Hz  to  P00.03  (max.  output 
frequency). 
P08.08  indicates  the  time  the  VFD  takes  to 
decelerate from P00.03 (max. output frequency) to 0 
Hz. 
Setting range: 0.0–3600.0s 
When the set  frequency is in the  range of jumping 
frequency,  the  VFD  will  run  at  the  edge  of  the 
jumping frequency.   
The VFD can avoid the mechanical resonance point 
by setting the jumping frequency. The VFD can set 
three  jumping  frequency.  But  this  function  will  be 
invalid if all jumping points are 0.   
Set frequency f
Time t
Jump 
frequency 2
1/2* jump amplitude 2
1/2* jump amplitude 2
Jump 
frequency 1
1/2* jump amplitude 1
1/2* jump amplitude 1
Jump 
frequency 3
1/2* jump amplitude 3
1/2* jump amplitude 3
Jumping frequency 
range 1 
Jumping frequency 
range 2 
Jumping frequency 
range 3