Detailed instruction of parameters 
Setting  range:  0.00  Hz–P00.03  (max.  output 
frequency) 
Overvoltage stall 
modulator gain 
Setting range: 0.0–1000.0 
Setting range: 0.00–10.00s 
Max torque of inertia 
compensation 
Limit  the  max.  inertia  compensation  torque  to 
prevent the inertia compensation torque from being 
too large. 
Setting  range:  0.0–150.0%  (rated  torque  of  the 
motor) 
Inertia compensation 
filter times 
Filter times of inertia compensation torque is used to 
smooth the inertia compensation torque. 
Setting range: 0–10 
High-frequency ACR 
proportional 
coefficient 
In the closed-loop vector control  mode (P00.00=3), 
when the running frequency is lower than  the ACR 
high frequency switching point (P08.21), the ACR PI 
parameters  are  P03.09  and  P03.10;  and  when the 
running  frequency  is  higher  than  the  ACR  high 
frequency  switching  point,  the  ACR  PI  parameters 
are P08.19 and P08.20. 
Setting range of P08.19: 0–20000 
Setting range of P08.20: 0–20000 
Setting range  of  P08.21:  0.0–100.0%  (relative max 
frequency) 
High-frequency ACR 
integral coefficient 
ACR high frequency 
switching point 
Inertia identification 
torque 
Because  of  the  friction,  it  is  necessary  to  set 
identification torque for normal inertia identification. 
0.0–100.0% (rated torque of the motor) 
0: No operation   
1:  Starting  identification:  press  "RUN"  to  enter  into 
the program after starting identification until display 
"-END-";  the  identified  system  inertia  is  saved  in 
P08.24. 
The  identified  system  inertia  can  be  set  manually 
when  the  system  inertia  is  known.  The  displayed 
system inertia may be less  than 0.001kgm
2
  for  the 
motors below 1 kW. 
Setting range: 0.000–30.000 kgm
2