Goodrive35 Series Closed-loop Vector Control VFD  Function parameters 
53 
Detailed instruction of parameters 
P01 Group Start-up and stop control   
0: Start-up directly: start from the starting frequency 
P01.01   
1: Start-up after DC brake: start the motor from the 
starting frequency after DC brake (set the parameter 
P01.03 and P01.04). It is suitable in the cases where 
reverse  rotation  may  occur  to  the  low  inertia  load 
during starting. 
2:  Start-up  after  speed  tracing:  start  the  rotating 
motor smoothly after tracking the rotation speed and 
direction  automatically.  It  is  suitable  in  the  cases 
where reverse rotation may occur to the big inertia 
load during starting.   
Note: The VFDs above 4 kW have the function. 
Starting frequency of 
direct start 
Starting  frequency  of  direct  start-up  means  the 
original  frequency  during  the  VFD  starting.  See 
P01.02 for detailed information.   
Setting range: 0.00–50.00 Hz 
Retention time of 
starting frequency 
fmax
t1
f1 set by P01.01
f1
t1 set by P01.02
Frequency f 
Time t
 
Set  a  proper  starting  frequency  to  increase  the 
torque  of  the  VFD  during  starting.  During  the 
retention  time  of  the  starting  frequency,  the  output 
frequency of the VFD is the starting frequency. And 
then, the VFD will run from the starting frequency to 
the set frequency. If the set frequency is lower than 
the starting frequency, the VFD will stop running and 
keep in the stand-by state. The starting frequency is 
not limited in the lower limit frequency.   
Setting range: 0.0–50.0s 
The brake current 
before starting 
The VFD will carry out DC brake at the brake current 
set before starting and it will speed up after the DC