Goodrive35 Series Closed-loop Vector Control VFD  Function parameters 
61 
Detailed instruction of parameters 
updated  by  autotuning, 
please count according to 
the following method.   
The  counter- 
electromotive  force 
constant  can  be  counted 
according  to  the 
parameters  on  the  name 
plate of  the  motor.  There 
are three ways to count:   
1.  If  the  name  plate 
designate  the 
counter-electromotive 
force constant Ke, then:   
E= (Ke*n
N
*2π)/ 60 
2.  If  the  name  plate 
designate  the 
counter-electromotive 
force  constant  E’ 
(V/1000r/min), then:   
E=E’*n
N
/1000 
3. If the name plate  does 
not  designate  the  above 
parameters, then:   
E=P/√3*I 
In the above formulas: n
N
 
is  the  rated  rotation 
speed,  P  is  the  rated 
power  and  I  is  the  rated 
current.   
Setting range: 0–10000 
control,  which  will  impact 
the  control  performance 
directly. 
When  P00.15=1  (rotary 
autotuning), the set value 
of P02.23 can be updated 
automatically  via 
autotuning;  when 
P00.15=2  (static 
autotuning), the set value 
of  P02.23  cannot  be 
updated  via  autotuning, 
calculate  the  value  of 
P02.23  and  update  it 
manually. 
Motor 1 overload 
protection   
0: No protection 
1:  Common motor  (with  low  speed  compensation). 
Because  the  heat-releasing  effect  of  the  common 
motors will be weakened, the corresponding electric 
heat  protection  will  be  adjusted  properly.  The  low