speed compensation characteristic mentioned here 
means  reducing  the  threshold  of  the  overload 
protection of the motor whose  running frequency is 
below 30 Hz.   
2:  Variable  frequency  motor  (without  low  speed 
compensation) Because the heat-releasing effect of 
the specific motors won’t be impacted by the rotation 
speed,  it  is  not  necessary  to  adjust  the  protection 
value during low-speed running.   
Motor overload multiple M = Iout/(In × K) 
In is the rated current of the motor, Iout is the output 
current  of  the  VFD  and  K  is  the  motor  overload 
protection coefficient. 
The  smaller  K  is,  the  greater  M  is,  and  the  more 
likely protection is implemented. 
When M=116%, protection is performed after motor 
overload lasts for 1 hour; when M=150%, protection 
is  performed  after  motor  overload  lasts  for  12 
minutes;  when  M=180%,  protection  is  performed 
after  motor  overload  lasts  for  5  minutes;  when 
M=200%,  protection  is  performed  after  motor 
overload lasts for 60 seconds; and when M≥  400%, 
protection is performed immediately.