Goodrive170-PV Series Solar Pump Inverter Function parameter list
-31-
Function
code
Name
Description
Default
Modify
14: Overload pre-alarm
1519: Reserved
20: External fault is valid
21: Reserved
22: Running time reached
23: Modbus communication virtual terminal
output
2463: Reserved
27: In weak light
28: Automatically switches from automatic
switching mode to power frequency input
mode
29: Forcibly switches to power frequency input
mode
30: Switches to PV input mode
P06.05
Output
terminal
polarity
selection
Used to set the polarity of output terminals.
When a bit is 0, the output terminal is positive.
When a bit is 1, the output terminal is negative.
BIT1
BIT0
RO2
RO1
Setting range: 0F
0
P06.10
RO1
switch-on
delay
0.00500.00s
10.00s
P06.11
RO1
switch-off
delay
0.00500.00s
10.00s
P06.12
RO2
switch-on
delay
0.00500.00s
0.00s
P06.13
RO2
switch-off
delay
0.00500.00s
0.00s