Goodrive20-EU series VFD Function parameters
40
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
stand-by state. The starting frequency is not
limited in the lower limit frequency.
Output frequency
fmax
t1
T
f1 set by P01.01
f1
t1 set by P01.02
Setting range: 0.0 50.0s
P01.03
Braking current
before starting
The VFD will carry out DC braking at the braking
current set before starting and it will speed up
after the DC braking time. If the DC braking time
is set to 0, the DC braking is invalid.
The stronger the braking current, the bigger the
braking power. The DC braking current before
starting means the percentage of the rated
current of the VFD.
Setting range of P01.03: 0.0 100.0%
Setting range of P01.04: 0.00 50.00s
0.0%
P01.04
Braking time
before starting
0.00s