Goodrive300-01A series VFD for air compressor Function code description
-57-
Function
code
Name
Parameter description
Default
value
Modify
1: Maintenance required; 0: Normal
BIT5: Auxiliary pressure signal
1: Auxiliary pressure signal fault; 0: Normal
BIT6: Auxiliary temperature signal
1: Auxiliary temperature signal fault; 0: Normal
BIT7: Auxiliary pressure pre-alarm signal
1: Pressure pre-alarm; 0: Normal
BIT8: Auxiliary temperature pre-alarm signal
1: Temperature pre-alarm; 0: Normal
BIT9: Auxiliary pressure alarm signal
1: Pressure alarm; 0: Normal
BIT10: Auxiliary temperature alarm signal
1: Temperature alarm; 0: Normal
BIT11: Maintenance timeout remainder
1: Maintenance timeout remainder; 0: Normal
BIT12: Phase sequence remainder
1: Fault; 0: Normal
P19.15
Device state
0: Standby
1: Run
2: Fault
3: Emergency stop
4: Undervoltage
5: Alarm
6: Sleep
7: In stop
8: Restart delay
0
P19.16
Accumulated running
time of the equipment
Display range: 065535h
0
P19.17
Accumulated
load-carrying running
time
0
P19.18
Restart count-down
Display the remaining time of restart delay.
After the system stops, it will enter restart
delay state and restart count-down to prevent
immediate restart. After restart delay time is
up, the system enters standby state. Under
standby state, start command can be
received.
Setting range: 03600s
0s
P19.19
Output value of
Display the output value of temperature PID
0.00%