How do I fix a motor autotuning fault on INVT Goodrive300-01A DC Drives?
- RRobert GordonSep 2, 2025
If your INVT DC Drive is experiencing a motor autotuning fault, the motor capacity might not match the VFD capacity, so change the VFD model. The motor parameters might be set improperly; set the motor type and nameplate parameters correctly. Finally, if the deviation between the parameters obtained from autotuning and the standard parameter is huge, empty the motor load and identify again.