Goodrive350-19 series VFD Function parameter list
- 295 -
Pull-in current is the pole position orientation
current; pull-in current 2 is valid within the upper
limit of pull-in current switch-over frequency
threshold, and you do not need to change pull-in
current 2 under common situations.
Setting range: 0.0%–100.0% (rated motor current)
Switch-over
frequency of input
current
0.00Hz–P00.03 (Max. output frequency)
High-frequency
superposition
frequency
(reserved)
This parameter is used to set the pulse current
threshold when the initial magnetic pole position is
detected in the pulse mode. The value is a
percentage in relative to the rated current of the
motor.
Setting range: 0.0–300.0% (of the rated voltage of
the motor)
This parameter is used to set the frequency
threshold for enabling the counter-electromotive
force phase-locked loop in SVC 0. When the
running frequency is lower than the value of this
parameter, the phase-locked loop is disabled; and
when the running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0–655.35