Goodrive350-19 series VFD Function parameter list
- 295 -
Function
code
Name
Description
Default
value
Modify
P13.03
Pull-in current 2
Pull-in current is the pole position orientation
current; pull-in current 2 is valid within the upper
limit of pull-in current switch-over frequency
threshold, and you do not need to change pull-in
current 2 under common situations.
Setting range: 0.0%100.0% (rated motor current)
10.0%
P13.04
Switch-over
frequency of input
current
0.00HzP00.03 (Max. output frequency)
10.00Hz
P13.05
High-frequency
superposition
frequency
(reserved)
200Hz1000Hz
500Hz
P13.06
Pulse current
setting
This parameter is used to set the pulse current
threshold when the initial magnetic pole position is
detected in the pulse mode. The value is a
percentage in relative to the rated current of the
motor.
Setting range: 0.0300.0% (of the rated voltage of
the motor)
100.0%
P13.07
Reserved
variables
0.0400.0
0.0
P13.08
Control parameter
1
00xFFFF
0
P13.09
Control parameter
2
This parameter is used to set the frequency
threshold for enabling the counter-electromotive
force phase-locked loop in SVC 0. When the
running frequency is lower than the value of this
parameter, the phase-locked loop is disabled; and
when the running frequency is higher than that, the
phase-locked loop is enabled.
Setting range: 0655.35
2.00