EasyManua.ls Logo

INVT Goodrive350-19 Series - Page 305

INVT Goodrive350-19 Series
540 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Goodrive350-19 series VFD Function parameter list
- 298 -
Function
code
Name
Description
Default
value
Modify
to the upper computer at a delay after data
process is done by system.
P14.04
Communication
timeout period
0.0 (invalid) 60.0s
This parameter will be invalid if it is set to 0.0;
When it is set to a non-zero value, if the time
interval between current communication and the
next communication exceeds the communication
timeout period, the system will report "485
communication fault" (CE).
Under common situations, it is set to 0.0. In
systems which have continuous communication,
you can monitor the communication condition by
setting this parameter.
0.0s
P14.05
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
0
P14.06
Communication
processing action
0x000x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
0x00

Table of Contents

Related product manuals