Goodrive350-19 series VFD Troubleshooting
- 413 -
1. If there is power distribution grounding or ground stud on the site, ground the cabinet chassis of
the drive system through the power ground or stud.
2. If there is no grounding on the site, you need to connect the motor chassis to the ground terminal
PE of the VFD, and ensure that the jumper at "EMC/J10" on the middle casing of the VFD is
shorted.