EasyManua.ls Logo

ISA T1000 PLUS - Page 102

ISA T1000 PLUS
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC. MIE91093 Rev. 1.34 Page 102 of 145
As test starts, all voltages are modified from VN to Vf; the
three fault current should be injected at the same time. This is
not completely true with the three T1000 PLUS because of the
zero crossing feature: the three phases have zero crossings
that are time shifted by 6.66 ms. The following figure explains
the situation; this means that in first zone the trip time will be
increased by 13,3 ms.
1) Fault current
The current will be adjusted on all the faulty phases; its
value is the one selected by the operator (for instance, 10 A).
2) Healthy voltages phase angles
Choose the test angle in the R-X plane. If the distance relay is
set on the CT star point towards Busbar, the angle Φ(I-V) has
the same value but negative, otherwise it has the same value.
These angles are adjusted prior to actual zone testing, as
follows.
Start the test; adjust the fault current; adjust the fault voltage
at 30 V. Now select on all T1000 PLUS the auxiliary Vac phase
with respect to the current, as follows:
AUX VAC/DC > Aux Vac control > Phase > Reference:
current ESC
This adjustment will not be modified during tests.
6.66 ms
PHASE 1
PHASE 2
PHASE 3

Table of Contents

Other manuals for ISA T1000 PLUS

Related product manuals