EasyManua.ls Logo

ISA T1000 PLUS - Page 27

ISA T1000 PLUS
145 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
DOC. MIE91093 Rev. 1.34 Page 27 of 145
There's an easy way to check the power transformer vector
group. Please make reference to the following wiring diagram.
Connect V main to the transformer HV side phase 1 and
2 (positive and negative).
Connect V aux to the transformer HV side phase 2 and
3 (positive and negative).
Adjust the same voltage value on both generators.
Adjust 240° for Vaux with respect to the mains.
Connect the measuring input Ext V (the 600 V or the
10 V input, as a function of the transformer ratio) to LV
side terminals 1 and 2.
Select the measurement of the ExtV - Vmain phase
angle.
This way, we are generating a three phase voltage on HV side,
all voltages with 120° phase shift. But, since phase angle of
V12is 0°, the phase shift measured on ExtV per respect to
Vmain, divided by 30, gives you the transformer group.
Suppose you measure 150°, the transformer group would be
150/30=5.

Table of Contents

Other manuals for ISA T1000 PLUS

Related product manuals