DOC. MIE91093 Rev. 1.34 Page 34 of 145
. Power-on T1000 PLUS, acting on switch (2): the internal light
turns on.
. Press the button (70) to have the AC voltage available.
. Set the current adjustment knob (6) completely counter-
clockwise.
. If you wish to use the DC voltage output to supply the relay
under test, press the button (69), then use knob (20) to
adjust the voltage value, that is displayed on the LCD display
(23). Connect the DC supply input of the relay to sockets (63).
. First select the auxiliary AC voltage range, as follows.
AUX VAC/VDC > Aux VAC control > Range (ESC)
The range should be the closest one to the high threshold to
be generated. The fault amplitude is adjusted by the multi-