7.0 Specifications (cont.)
Input
Voltage 120 or 277 VAC User Selectable
Current 2.7A (120V), 1.2A (277V) for 250 Watt Model
1.4A (120V), 0.6A (277V) for 125 Watt Model
Frequency 60Hz +/- 2 Hz
Protection Easy access 8A fast acting 5x20 mm fuse.
Power Factor 0.5 lead to 0.5 lag
Output
Voltage 120 or 277 VAC User Selectable
Current 2.08A (120V), 0.9A (277V) for 250 Watt Model
1.04A (120V), 0.45A (277V) for 125 Watt Model
Frequency 60Hz +/- 0.02 Hz crystal controlled during emergency mode
Overload 110 percent will generate overload fault
Transfer Time 50mS standard (Optional 1 Second)
Output Distortion Less than 3% THD
Crest Factor 10X for 125W and 5X for 250W model
Load Power Factor 0.5 lead to 0.5 lag
Output Types 1x Normally-On, 3x Multipurpose Normally-Off/Switched
Battery
Type Premium Long Life Valve-Regulated Lead Acid (VRLA)
Charger 3 rate with Temperature Compensation
Recharge Time 24 Hour recharge standard
Protection Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC
Automatic restart upon utility return
Runtime 90 Minutes at 25 °C
DC Voltage 24 VDC Nominal, 2.27 VPC float, temperature compensated
DC Current 6.2/12.4 ADC Nominal for 125W/250 Watt model respectively
Environmental
Operating Temp 20 to 30 °C
Storage Temp -20 to 70 °C (Electronics)
0 to 40 °C (Batteries)
Relative Humidity <95 % (non-condensing)
Physical
Cabinet NEMA Type 1 enclosure, 16 AWG powder painted CRS
Cooling Natural Convection No fans
Size/Weight 15.4W-12H-4.25D / 33lbs. (125W Model)
15.4W-17.3H-4.25D / 57 lbs. (250W Model)