DCM600 to 1800 - Instruction Manual
Figure 1
EXTENSION CANAL
ESCLAVE
SOLÉNOÏDES
ENTRÉE
LIGNE
SPECIFICATIONS
Pressure Ranges: ........................ 10˝ w.c. or 20˝ w.c.
Temperature Limits: ......................-40 to 140°F (-40 to 60°C).
Pressure Limit: ............................. 10 psi (68.95 kPa).
Pressure Limit (dierential): ...... 10 psi (68.95 kPa).
Accuracy: ...........................................±1.5% F.S. @ 73°F(22.8°C).
Output Signal: ................................. 4-20 mA.
Alarm Contacts: ........................... 1.5 A inductive load, 3 A resistive load @ 30 V AC or 40 V DC.
Process Connections: ...................Two barbed connections for use with 1/8˝ (3.18 mm) or 3/16˝ (4.76 mm) I.D.
tubing.
Switch connections
Figure 1
MASTER
CONTROLLER
TO ADDITIONAL
EXPANDER
MODULES
SLAVE CHANNEL
EXPANDER
SOLENOÏDS
ENTRÉE
LIGNE
MASTER CONTROLLER
INPUT MUST NOT BE
CONNECTED
NORM
ALLY
OPEN
CONTACTS
C
ONNECTIONS 4-20mA
SERIES DCP100A/200A PRESSURE MODULES
SPECIFICATIONS INSTALLATION & OPERATING INSTRUCTIONS
The DCP100A or DCP200A pressure
modules are designed exclusively for
use with the Dwyer DCT1000 Dust
Collector Timer Controller boards for
on-demand cleaning requirements.
These series of modules are available
in 10’’ w.c. [2.49 kPa] or 20’’w.c.
[4.98 kPa] ranges, which allow
for dierential process pressure
measurement as indicated on the
display of the master controller. An
isolated 4-20 mA readout channel is
provided for remote pressure display. The 4-20 mA output may be wired either for use with an external power
supply and indicator or using the isolated on-board 24 volt power supply to power the loop.