EasyManua.ls Logo

ITech IT6302 - Additional Features

ITech IT6302
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IT6302 user manual
USER MANUAL
14
2.2 Additional features
Suggested calibration frequency: 1time /Year
Line voltage supported (can be selected by the switch on the rear panel)
Option 01: 220VAC ± 10%, 47 to 63 Hz
Option 02: 110 VAC ± 10%, 47 to 63 Hz
Max input power
Module
IT6302
Power
750VA
Cooling
Fans
Operation temperature
0 to 40 °C
Storage temperature
-20 to 70 °C
Environmental conditions
Indore use only, max humidity 80%, no condensation.
Setup stability-8h
(%of Output +Offset)
Voltage
0.01%+10mV
Current
0.1%+5mA
Readback stability-8h
(%of Output +Offset)
Voltage
0.01%+20mV
Current
0.1%+5mA
Fuse specification
6.3A(110V)/3.15A(220V)
Command Response
Time
20mS (Typical)
Power Factor
0.7 (Typical)
Maximum input current
4.5A(110V)/2.2A(220V)
Maximum input
apparent power
700VA
Storage temperature
-10~70
Protective function
LVP/OTP
standard Interface
COM(TTL)
Isolation
( output to ground)
200V
Working temperature
0~40
Dimension ( mm)
214.5mmW*88.2mmH*354.6mmD
Weight( net)
7.1Kg

Related product manuals