91
UMG 806www.janitza.com
Function Symbol Accuracy class Display range
Norm
Voltage U 0.2 0-999.9 kV
IEC61557-12
Current I 0.2 0-99,99 kA
IEC61557-12
Active power P 0.5 0-9999 MW
IEC61557-12
Reactive power Q 0.5 0-9999 Mvar
IEC61557-12
Apparent power S 0.5 0-9999 MVA
IEC61557-12
Power factor PF 0.5 0-1.000
IEC61557-12
Frequency F ±0.01 Hz 45.00 Hz-65.00 Hz
IEC61557-12
Active energy EP 0.5 s 0-99999999 MWh
IEC62053-22
Reactive energy EQ 2 0-99999999 Mvarh
IEC62053-23
Harmonic ratio of voltage THDu
1 (50 Hz)
5 (60 Hz)
0-99.99 %
IEC61557-12
Harmonic ratio of current THDi 0-99.9 9%
IEC61557-12
Sub-harmonic voltage component THDu 0-99.99 %
IEC61557-12
Sub-harmonic current component THDi 0-99.99 %
IEC61557-12
Voltage unbalance Uunb 0.5 --
IEC61557-12
Current unbalance Iunb 0.5 --
IEC61557-12
Phase sequence of the mains voltage -- 0.5 --
IEC61557-12
Phase position of the mains voltage /
mains current
-- ±0.1°
IEC61557-12
Phase sequence of the mains current -- 0.5 --
IEC61557-12
Extreme value -- 0.5 --
IEC61557-12
Consumption -- 0.5 --
IEC61557-12
Temperature T ±2° C --
--
16.3 Technical data of the modules
Transport and storage
The following specifications apply for devices transported and stored in the original packaging.
Free fall 1 m (39.37 in)
Temperature -40 °C (-40 °F) to +85 °C (185 °F)
Relative humidity 5 to 95 % RH at 77 °F (25 °C), non-condensing
Environmental conditions during operation
The device:
For weather-protected and stationary use.
Fulfills operating conditions according to DIN IEC 60721-3-3.
Has protection class II according to IEC 60536 (VDE 0106, part 1), a ground wire connection is not required!
Rated temperature range -40 °C (-40 °F) to +70 °C (158 °F)
Relative humidity 5 to 95 % at 77 °F (25 °C), non-condensing
Operating elevation < 2500 m (8200 ft) above sea level
Pollution degree 2
Ventilation No forced ventilation required.
Protection against foreign matter and water IP20 according to EN60529
806-EC1 module
Ethernet communication module
Interface RJ45 (10M)
Transmission technology IEE 802.3
Operating mode Server
MAC IEEE certification
IP Static, DHCP
Protocol Modbus/TCP, SNMP V2c
Function Modbus gateway
Isolation voltage 1.5 kV AC
General
806-EC1 806-EI1 806-ED1
Net weight
approx. 82 g
(0.18 lbs)
approx. 91 g
(0.20 lbs)
approx. 82 g
(0.18 lbs)
Device dimensions
Approx. B = 36 mm (1.42 in), H = 90 mm (3.54 in),
D = 63.5 mm (2.5 in)
Mounting orientation As desired
Installation - suitable DIN rails - 35 mm (1.38") According to EN 60715
Impact resistance IK04 according to IEC 62262

Table of Contents