JOHNSON CONTROLS
43
SECTION 12 - BACNET MS/TP POINTS
FORM 100.50-SU8
ISSUE DATE:1/28/2016
12
BACNET NAME
USER
INTERFACE
NAME
READ/
WRITE
BACNET/
OBJECT TYPE
AND INSTANCE
MODBUS
REGISTER
ADDRESS
POINTS LIST DESCRIPTION
RDY_STOP_C1B
READY TO
STOP COMP 1B
STATUS
R BI47 1328
DISPLAYS THE STATUS OF
COMP 1B READY TO STOP IF
OPERATING: YES/NO
RDY_STOP_C2A
READY TO
STOP COMP 2A
STATUS
R BI48 1329
DISPLAYS THE STATUS OF
COMP 2A READY TO STOP IF
OPERATING: YES/NO
RDY_STOP_C2B
READY TO
STOP COMP 2B
STATUS
R BI49 1330
DISPLAYS THE STATUS OF
COMP 2B READY TO STOP IF
OPERATING: YES/NO
RDY_STOP_C3A
READY TO
STOP COMP 3A
STATUS (70-150
TON ONLY)
R BI50 1331
DISPLAYS THE STATUS OF
COMP 3A READY TO STOP IF
OPERATING: YES/NO
RDY_STOP_C3B
READY TO
STOP COMP 3B
STATUS (70-150
TON ONLY)
R BI51 1332
DISPLAYS THE STATUS OF
COMP 3B READY TO STOP IF
OPERATING: YES/NO
RET_AIR_BY_S
RETURN AIR
BYPASS ACTIVE
SP
R AI37 550
DISPLAYS THE VALUE (%) FOR
THE CURRENT SP OF THE
RA BYPASS DAMPER ON A
FLEXSYS UNIT
RET_AIR_ENTH
RETURN AIR
ENTHALPY
R AI38 551
DISPLAYS THE ACTUAL RA
ENTHALPY (BTU/LB)
RET_AIR_HUMD
RETURN AIR
HUMIDITY
R AI39 552
DISPLAYS THE ACTUAL RA
RELATIVE HUMIDITY (%)
RET_AIR_TEMP
RETURN AIR
TEMP CURRENT
R AI40 553
DISPLAYS THE ACTUAL RA
TEMP (°F)
RET_FAN_OUT
EXHAUST/
RETURN FAN
VFD
R AI41 554
DISPLAYS THE OUTPUT FROM
THE CONTROL TO THE EXH OR
RET FAN VFD (%)
RET_FAN_PRES
RETURN FAN
PRESSURE
CURRENT
R AI42 555
DISPLAYS THE ACTUAL
PRESSURE THAT IS USED TO
CONTROL THE RETURN FAN
SPEED ("W.C.)
RET_FAN_STAT
RETURN FAN
STATUS
R BI52 1333
DISPLAYS THE STATUS
OF THE RETURN FAN RUN
VERIFICATION CIRCUIT:
0=STOP/VERIFICATION CKT
OPEN, 1=RUN/VERIFICATION
CKT CLOSED
RST_ENT_BAS
RESET
ENTHALPY SP
BAS (FLEXSYS)
R/W AV41 1066
DISPLAYS THE RA ENTHALPY
SP WHICH CAUSES THE UNIT
TO SWITCH FROM THE EVAP
LEAVING HIGH SP TO THE EVAP
LEAVING LOW SP
SAT_HIGH_LIM
SUPPY AIR
TEMP HI SP
R/W AV26 1051
DISPLAYS THE UPPER LIMIT
FOR THE SUPPLY AIR TEMP SP
ON A VAV UNIT (°F)
TABLE 1 - BACNET MS/TP POINTS (CONT'D)